Zs: what you check it againstYour B32 reads 1.2 ohms on test. Pass?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Record Zs in column 27 of the schedule of test results, then compare it with the maximum. Here’s the bit that loses marks: check it against the maximum measured value, not the maximum tabulated one.

Tabulated BS 7671 Tables 41.2–41.4 at operating temperature B32 · 1.37 Ω Measured (≈80%) GN3 · On-Site Guide a cold circuit, on test B32 · 1.09 Ω your reading on test ≤ the measured maximum
The cable you test is cold, at about room temperature. In use, current warms it and its resistance rises. The measured maximum leaves room for that rise; the tabulated figure assumes it has already happened.

The tabulated maximum is what you wrote on the schedule of circuit details. If you used a measured value from Guidance Note 3 or the On-Site Guide there instead, say so in the remarks.

BS 7671 · Tables 41.2–41.4 · maximum Zs On-Site Guide · Table B6 · the 80% values

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside