Ze, Zdb and Zs: where each one is doneWhere is Zdb measured?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Three values, three places, and the middle one gets mixed up most.
| Value | Where | Parallel paths |
|---|---|---|
| Ze | At the origin — your main board, across the incoming supply | Removed — earthing conductor disconnected |
| Zdb | At any other board — garage, workshop, summer house | Left connected |
| Zs | At every circuit, at the point of utilisation | Left connected |
✋Zdb is measured at each board other than the main one. It is the Zs of a distribution circuit, measured at the board that circuit feeds. If a property has three or four boards you will have three or four Zdb values — and three or four test sheets, each carrying its own. For the main board itself, the Zdb box on the schedule takes your Ze.
Zs can be calculated instead of measured. Ze + (R1 + R2) saves you climbing into a loft to reach a lighting point. Both are accepted.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing