Ze: the external impedance, and what you are not allowed to touchCan you put your leads in the meter tails?
Free from the notes: the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Ze is everything outside your installation — the supply transformer, the service cable and the earth return path. You are testing the DNO's supply, not your own work. Guidance Note 3 · p.84.
Which raises the question of where you are allowed to put your leads:
| Point | May you touch it? |
|---|---|
| DNO cutout / service head | No — illegal |
| The kWh meter and its tails | No — the DNO's |
| The electricity company's isolator | You may lock off there, but not disconnect inside it |
| Incoming terminals of your main switch (usually the top) | Yes — the closest legal point to the incoming tails |
| Incoming terminals of a separate isolator, if fitted | Yes — you can take the measurement there instead |
Say the reading comes back at Ze = 1.09 Ω on a TN-C-S supply, which is very high for that system type — which is exactly the point of measuring it rather than assuming it.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing