A 10 kW load on a 230 V TN-S system

1 · Design current
Ib = P ÷ V
Ib = 10 000 ÷ 230
Ib = 43.48 A   (the full load current — everything on at once)

2 · Protective device
The rule:  Ib ≤ In
The next size up from 43.48 A is In = 50 A, type B circuit breaker

3 · Disconnection time
Final circuit over 32 A supplying only fixed equipment
→ Reg 411.3.2.3: up to 5 seconds (TN)
(If the cooker control unit has a socket-outlet, it's a ≤ 63 A
circuit with a socket → Table 41.1, 0.4 s.)

4 · Maximum Zs
Table 41.3, type B, 50 A (one value for both times, Reg 411.4.202)
0.87 Ω tabulated (circuit in use)

5 · What you should measure on a new circuit
0.87 × 0.8 = 0.70 Ω   (or read it straight from OSG Table B6)

6 · Fault current needed to trip it
Type B = 5 × In (worst case)
50 × 5 = 250 A
✓If the Zs of that purple fault path in service does not exceed 0.87 Ω (0.70 Ω measured on the new, cold circuit), the breaker will operate inside the permitted disconnection time, and ADS is achieved. That's the entire chain, in one sentence.
A reality note on Ib. 43.48 A assumes every ring, the grill and the oven all running flat out at once — a Christmas dinner, not a Tuesday. In real design you'd apply diversity (maximum demand), which is why the On-Site Guide's Appendix A will happily let you put a 15 kW domestic cooker on a 32 A breaker. That's a later module.

Ib ≤ In · device rating must be at least the design current 411.3.2.3 · 5 s (TN) · or Table 41.1, 0.4 s, with a socket on the control unit Table 41.3 · 0.87 Ω On-Site Guide · Appendix A · diversity

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside