Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Ipf is the most current that could flow in a fault at that point. Every protective device has a limit to what it can safely interrupt, printed on it: the number in the small rectangle — 6000 means an Icn of 6 kA.

RatingWhat it means
IcnThe most fault current it can interrupt safely — though it may not be fit to use afterwards
IcsThe most it can interrupt and still work as before. Equal to or lower than Icn
✋Compare Ipf with every device’s Icn. A device’s breaking capacity must be at least the prospective fault current where it is installed. If it isn’t, the device is not suitable: the installer chooses devices with a higher breaking capacity; they’re made well beyond 6 kA.

Guidance Note 3 · 2.6.16 · Icn and Ics of protective devices

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside