Why 82 Ω cannot achieve ADSCan any breaker clear an 82 ohm loop?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Take that 82 Ω and go looking for a protective device that will disconnect in time. Check BS 7671 · Tables 41.2 to 41.4:
| Device | Highest Zs in the table |
|---|---|
| Fuses | around 44 Ω, dropping as the rating rises |
| Type B circuit breakers | around 14.5 Ω |
| Type C | around 3.64 Ω |
So with an RA that high, no fuse and no circuit breaker will achieve automatic disconnection of supply. And remember your RA is only the start — add a circuit's R1 + R2 and Zs is higher still.