Where 0.87 Ω comes fromWhere does the 0.87 ohm in Table 41.3 come from?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Where 0.87 Ω actually comes from

Table 41.3 gives a 50 A type B breaker a maximum Zs of 0.87 Ω, so where does that number come from? It isn't arbitrary — it's calculated, and the formula is printed in the book at Reg 411.4.4 (p.73) as Zs × Ia ≤ U₀ × Cmin, and again at 411.5.4, under Table 41.5 (p.77). Rearranged, it reads:

Zs ≤ (U₀ × Cmin) ÷ Ia
U₀ = nominal voltage to earth, 230 V · Cmin = 0.95 · Ia = the current that operates the device in the required time

Proving the 0.87 Ω for a 50 A type B

Ia for a type B = 5 × In
Ia = 5 × 50 = 250 A

Zs ≤ (230 × 0.95) ÷ 250
Zs ≤ 218.5 ÷ 250
Zs ≤ 0.874 Ω

Table 41.3 says 0.87 Ω. Same number.

Cmin is 0.95 and it's the minimum voltage factor, defined at 411.4.4 to take account of voltage variations; Note 1 there gives 0.95 for low voltage supplies. Don't lose sleep over where 0.95 came from — it's a given value — accept it and move on.

You will not have to do this in the job. A designer works these out; an installer or tester works to the 80 % measured value instead. It's here so the tables stop looking like magic.

411.4.4 · p.73 · Zs × Ia ≤ U₀ × Cmin 411.5.4 · under Table 41.5 · p.77 411.4.4 · Note 1 · Cmin = 0.95

Ia: the current that trips the device

The book defines Ia as the current causing automatic operation of the protective device within the required disconnection time. In plain terms: how much fault current it takes to make it trip in time, which is what achieves ADS.

Breaker typeIa50 A example
Type B5 × In250 A
Type C10 × In500 A
Type D20 × In1000 A
Iₐ — how much it takes to trip in time the same 50 A rating, three different types Type B 5 × Iₙ 250 A Type C 10 × Iₙ 500 A Type D 20 × Iₙ 1000 A 0 250 500 750 1000 amps
Same 50 A rating, four times the fault current between a type B and a type D — which is why the type matters as much as the size. If the loop impedance cannot deliver that current, the device will not disconnect in time and ADS is not achieved.

You can also read Ia straight off Appendix 3. It prints, with each set of time/current curves, a table of the currents needed for operation between 0.1 s and 5 s — those figures are the Ia values. For a type B the tabulated figure is simply five times the rating.

≡So the three ideas connect: Ia is how much current it takes to trip · Zs decides how much current can actually flow · if Zs is low enough, the fault current reaches Ia and ADS happens.

Appendix 3 · Figure 3A4 · time/current curves and the operating-current tables

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside