When an RCD has to be replacedThe test button does nothing. Now what?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
If the test button does not work, replace the device

The device's own test button creates a small imbalance between line and neutral. If pressing it does not trip the RCD, you do not carry on with the RCD tests — the device gets replaced at the inspection stage.

Domestic RCDs are 30 mA. You would not change to 100 mA in a house — 30 mA is what the guidance asks for and more than enough.
Nuisance tripping is a different problem. That may mean you need a different type of RCD rather than a different rating — and types have changed as technology has.
Cost is a real factor in the advice you give. An AFDD is around £120 a device. BS 7671 sets out where they are required; outside that it is a judgement call for the client, not an automatic recommendation.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside