What safe isolation is, and the kitIs switching off the main switch safe isolation?

Free from the notes: the section word for word as members see it, and a PDF to keep.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
§Safe isolation means establishing that while you're working, you cannot be harmed — nobody can come past and re-energise the installation you're on, and they're kept out of the way by more than one means.
✋It is not just "turn the supply off". Not pulling the supplier's cut-out fuse, not just flicking the main switch. There is a procedure, and it has a lot of steps. Best Practice Guide 2 from Electrical Safety First sets the whole thing out — the kit, the standards, the voltages, what's allowed. It's a free download and it's worth having.

Before anything else: the barrier you put up. What kind of protection is that? Basic protection — stopping you coming into contact with a live part in the first place. The consumer unit's own cover is basic protection too, for you and for everyone else when you're not there.

What's in the kit

ItemWhat it's for
Approved voltage indicator (AVI)
A two-pole tester
Proving dead. An approved voltage indicator to BS EN 61243-3; GS38 covers its leads and probes
Proving unitA known source to prove the AVI works, before and after
Padlock and keyLocking off. The key stays in your pocket, on you, at all times
Lock-off devicesClip into an MCB to hold it off — plastic push-fit or brass with a small screw. The hole takes your padlock
Multi-lock haspOn a big site with several trades. It does not come off until the last lock is removed
Warning signs and barriersSo people can see it's locked out and they're not to switch it on
✋The single-pole tester is not for proving dead. A "fault stick" — a single-pole tester — is genuinely useful: an open PEN fault on a TN-C-S system is exactly what it's for. But it does not prove a circuit dead. Neither does a test screwdriver.

What GS38 actually asks of the leads

Flexible leadsIn good condition — no nicks, cuts, splices; not stiff; nothing missing. Length doesn't matter, flexibility does
Exposed probe tipNo more than 4 mm exposed — 2 mm or less preferred
Spring-loaded probesPreferred — the shroud pushes back as you press into a terminal
Finger guardsMust be in place. Missing or cracked, don't use them
Test lampsMust light. If they don't, there's a problem with the tester
One habit to avoid. Don't loop the lead behind your neck to keep it out of the way. Just keep it clear of what you're doing.

Electrician's Guide · Section 7 · 7.5 · safe isolation procedure ★ HSE GS38 · leads, tips, guards ★ Best Practice Guide 2 · Electrical Safety First · free download

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside