  • Conduit and other containment can carry most types of cable, but it's mostly used for single-core cables (singles). These have only one layer of insulation and no sheath.
  • Singles must be installed in containment, and conduit is perfect for it.
  • General rule for any containment, conduit or trunking: don't overfill it. For trunking, keep to the 45 % space factor in Appendix E of the On-Site Guide. For conduit, Appendix E uses cable factors and conduit factors instead.
  • There are calculations to work out exactly how many conductors fit in a given conduit or trunking. Those are beyond these notes.
air cables: max 45 % free space: at least 55 % Cable area ÷ internal area of the trunking ≤ 45 %. Room is left so cables can be drawn in without damage and heat can escape. See On-Site Guide Appendix E.
The idea behind the 45 % rule: cables take up no more than 45 % of the inside, so at least 55 % is left empty. (Drawing shows about 43 %.)
Watch out
A common mix-up is that Appendix E explains there should be "a 45 per cent gap" in the conduit. It's the other way round: cables may fill up to 45 % of the space (the space factor), leaving at least 55 % free. Also, Appendix E handles conduit with a cable factor / conduit factor method (which allows for bends and length of run) and uses the 45 % space factor for trunking. Check the tables in your own copy.

On-Site Guide · Appendix E · cable capacities of conduit and trunking (45 % space factor) Key reference: tab it

BS 7671 · Reg 521.10.1 · non-sheathed (single-insulated) cables must be enclosed in conduit, ducting or trunking

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside