Design isn't just picking any cable. It's based on the client's needs and on what's already there. Before adding or altering a circuit, check that the existing installation can:
- carry the additional load
- provide adequate shock protection
- has satisfactory earthing and bonding
Think of design as a chain. The load gives the design current, which decides the protective device, which with the installation method and conditions decides the cable size, which must then pass voltage drop. Example: if a client upgrades a shower from 5 kW to 8 kW, the existing cable may no longer be suitable.
BS 7671 · Appendix 1: British Standards and other standards referred to (about 22 pages) · p.411
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing