You cannot always get behind a socket to bypass it. A socket with USB outlets is the common case — and new builds are fitting them as standard, so you will meet it constantly.
What you do, and what you record
Cannot bypass -> test the circuit at 250 V, live conductors joined, to earth Then put it in the remarks, in words: "Downstairs ring tested at 250 V due to five sockets with USB outlets."