535 — protection against undervoltage

This is the device-selection end of 445, which you met in Part 4 earlier. The danger is what a drop or loss of voltage, and its return, can do: equipment restarting by itself when the voltage comes back, with someone's hands on it, or equipment being damaged by running on too low a voltage. The regulation is mostly framed around relays and motor circuits, but the principle applies to any circuit.

536 — coordination, also known as selectivity

Section 536 is headed coordination. Selectivity is the same idea under its other name, and it is defined in Part 2 (p.48). Know both words.

§536.1 — mutual interaction. Whatever overcurrent protective devices you use must coordinate with the protective and switching devices around them: RCBOs, contactors and starters, switch-disconnectors. They have to work together rather than fight each other.
  • Selectivity applies to overload conditions as well as short circuits and residual currents.
  • You can have selectivity between fuses and breakers, and between overcurrent devices and RCDs.
  • There is more than one way of achieving it, and the section lists options. 536.3 lists the requirements — that's the bit worth highlighting.

Don't confuse it with the problem from earlier: put too many circuits behind one 30 mA RCD and accumulated leakage trips it with no fault present. That isn't selectivity; it's a design and division-of-circuits problem (531.3.2: standing leakage no more than 30 % of IΔn).

538 — monitoring devices

This is where insulation monitoring devices (IMDs) for IT systems sit, alongside residual current monitoring. Don't muddle an IMD with an RCM — different job, different device.

There's another standard behind these. Reg 532.3 (p.168) says residual current monitors shall be in accordance with BS EN 62020. Being mentioned in BS 7671 doesn't mean BS 7671 is the whole requirement.

535 · devices for protection against undervoltage 536 · coordination / selectivity ★ 536.3 · the list of requirements 538 · monitoring devices · IMDs for IT systems 445 · undervoltage (Part 4)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside