Two-way switching

A two-way switch has 3 terminals: COM (common), L1 and L2. Pressing it doesn't turn it "on" or "off". It just swaps COM between L1 and L2. The two switches are linked by 3-core & earth cable (brown, black, grey plus a bare CPC). The two cores that link L1 to L1 and L2 to L2 are the strappers; the third core carries the common.

line from loop 2-way switch 2-way switch COM L1 L2 COM L1 L2 strapper (black, sleeved brown) strapper (grey, sleeved brown) 3-core & earth between the switches switch line to lamp
Both switches on L1 = closed = lamp on. Flip either switch = open = lamp off. Flip the other one too and it's on again.
  • Sleeve every strapper brown (black and grey), because they're all line conductors. You could buy all-brown 3-core, but then you couldn't tell which is which.
  • There's no right or wrong colour for COM, L1 or L2. Swap the two strappers (L1 and L2) at one end and it still works. What stops it working is mixing COM with a strapper, so keep COM to COM.
  • Coiling the CPC neatly in the back box is purely cosmetic. It adds length, and length means resistance.

On-Site Guide · Section 7 · Figure 7.4.4 two-way switching wiring (black in COM in that drawing) · p.107

Intermediate switching

To control a light from 3 or more places, fit intermediate switches between the two two-way switches. You can have as many as you need, e.g. a stairwell over several floors or a big room with several doors. They're mainly commercial, and rare in homes.

2-way Intermediate 2-way L1L1 L2L2 flips between straight-through and crossed COM conductor bypasses in a connector (e.g. Wago) L1 in / L1 out on the same side, L2 in / L2 out on the other. Never cross brown-to-brown horizontally.

Wire it as before, common to common. The common conductor (whatever colour you used in COM) doesn't connect to the intermediate. It just joins through in a connector in the back box. It isn't an earth.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside