Three-phase prospective fault current, worked throughWhy double the highest reading?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Guidance Note 3 · p.88 · 2.6.16, which covers single and three phase.

Line to neutral, one conductor at a time

L1 – N  =  398 A
L2 – N  =  402 A
L3 – N  =  405 A   <- highest

405 × 2 = 810 A = 0.81 kA

The reason for doubling: the worst case on three phase is a fault across all three lines (about twice the single-phase value), and on many instruments it cannot be measured directly — so the book has you double the highest single-phase reading, erring towards safety.

If your instrument CAN measure line to line, you do not double. You divide the measured line-to-line fault current by 0.87 instead.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside