The two-stage insulation resistance test (Reg 643.3.2)How do you test a circuit with sensitive equipment on it?

Free from the notes: the section word for word as members see it, and a PDF to keep.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

For circuits with equipment that would be damaged by the test, or would influence it, the insulation resistance test is done in two stages. The inspector identifies those circuits.

Stage 1 · before equipment NOT connected conductors joined in blocks 500 V · L–N, L–E, N–E these are the results you record Stage 2 · after equipment connected 250 V DC live conductors → earth only no L–N · at least 1 MΩ proves nothing changed
Stage 1 proves the wiring at full test voltage before anything vulnerable is on it. Stage 2 proves the connected installation to earth at a voltage that won’t harm the equipment — and never line to neutral, which would put the test voltage straight through it.
As the installer, plan for it. On circuits with vulnerable equipment or neon switches, join the conductors in connector blocks for the test, then second-fix the equipment. It’s ten minutes’ extra work, against damaging a two-thousand-pound piece of kit and explaining that to the client.
Lower test voltage, lower range. Some testers show a lower over-range figure at 250 V — >200 instead of >999. It’s still off the scale, and still a pass.

BS 7671 · Reg 643.3.2 · two-stage testing Guidance Note 3 · 2.6.7 · the two-stage test

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside