The two continuity test methods, and how to remember them
For continuity of protective conductors there are two test methods, and here is a way of never mixing them up:
| Method | What you connect | Used for |
|---|---|---|
| Method 1 | Line to cpc — R1 + R2 | A circuit's line and protective conductor together |
| Method 2 | R2 only — both leads on one conductor | Bonding conductors, or a cpc end to end |
And after those two comes a third continuity test with its own procedure: the ring final circuit.
Legs, and why only a ring has them
A term that gets used constantly once ring finals start, so it is worth pinning down.
| Circuit | Cables leaving the board |
|---|---|
| Ring final | Two — one going out, one coming back. Those are the legs. |
| Radial (lighting, cooker, immersion) | One — it goes out to the end point and stops. It does not return. |
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing