The Table 41.1 rule, and where to look in BS 7671Which circuits does Table 41.1 cover?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Where to look in BS 7671

This topic generates a lot of questions. The confusion is all in Chapter 41 of BS 7671 (protection against electric shock), where there are several different maximum disconnection times. The aim is to know which one applies to the circuit in front of you. Have your BS 7671 open around pages 71 and 72.

BS 7671 · Chapter 41 · Regulation 411.3.2.2 (which circuits use Table 41.1) · p.71 BS 7671 · Table 41.1 maximum disconnection times · p.72

BS 7671 · Regulations 411.3.2.3 (TN) and 411.3.2.4 (TT) · p.72 Have these two pages open for this whole masterclass

The Table 41.1 rule

Regulation 411.3.2.2 says the maximum disconnection times in Table 41.1 apply to final circuits with a rated current not exceeding:

Table 41.1 applies to final circuits of:
  • 63 A or less, with one or more socket-outlets
  • 32 A or less, supplying only fixed connected current-using equipment (a shower, a cooker, a heater…)

Turn that round, and you get the three cases where you don't use Table 41.1:

  1. The circuit isn't a final circuit (it's a distribution circuit, feeding another board).
  2. It's a final circuit supplying sockets above 63 A.
  3. It's a final circuit supplying fixed equipment above 32 A.
Sparky's tip
Keep saying it to yourself: Table 41.1 = final circuits, sockets up to 63 A, fixed equipment up to 32 A. Everything else goes to the two regulations that follow it.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside