The symbols you need coldIb, In, Iz, It. Which is which?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

I₂ and the 1.45 factor

A second formula worth knowing, from Reg 433.1.1(c) (p.103), and it explains a number people meet without understanding.

I₂ ≤ 1.45 × Iz
I₂ = the current that ensures effective operation of the device · 1.45 is a factor, not a current

For a circuit breaker, I₂ is 1.45 × In: the current at which it is sure to operate within the conventional time. On the Appendix 3 curve that sits in the slow thermal (overload) region, not the instantaneous part. So once In ≤ Iz, a circuit breaker meets I₂ ≤ 1.45 × Iz automatically.

A 6 A type B lighting breaker

Effective operation:  1.45 × 6  = 8.7 A
  → sure to trip, within the conventional time

Instantaneous trip:   5 × 6     = 30 A
  → operates within 0.1 s

A lighting circuit normally draws 2–3 A,
so 8.7 A is a long way above normal use.
!For a BS 3036 semi-enclosed rewireable fuse the rating factor is 0.725 — exactly half of 1.45, because a rewireable fuse needs about twice its rating to operate in the conventional time. Different device, very different behaviour.
Overload versus fault, on one graph. The long sweeping curve is the overload region — a modest excess can take a very long time to trip. The straight vertical part at the bottom is the fault region, where a big current trips it almost instantly.

433.1.1(c) · p.103 · I₂ ≤ 1.45 × Iz Appendix 3 · Figure 3A4

What 1.45 actually marks a 6 A type B breaker, along the current it is carrying carries it thermal region — the strip warms and bends it takes time, and the hotter it gets the faster it goes magnetic 6 A Iₙ · rated 8.7 A 1.45 × Iₙ 30 A 5 × Iₙ 0 10 20 30 amps 1.45 is a factor, not a current — at 1.45 × Iₙ the breaker is sure to operate, given time I₂ ≤ 1.45 × Iz is the overload check, Reg 433.1.1(c)
At its rated 6 A the breaker carries current all day. At 8.7 A — 1.45 times the rating — the breaker is sure to operate, but only within the conventional time, not instantly; the further above it you go, the quicker it operates. Only at 30 A, five times the rating, does the magnetic trip act instantly. People meet 1.45 as if it were an instant trip current; it is the factor that gives I₂, the current ensuring effective operation.

The symbols you need cold

Make sure you know these, and highlight them in the abbreviations list towards the end of Part 2.

SymbolMeansWhere it comes from
IbDesign currentCalculated from the load: P ÷ V
InNominal rating of the protective deviceChosen so Ib ≤ In
IzCurrent-carrying capacity of the cable in its installed conditionsIt × the correction factors
ItTabulated current-carrying capacityRead from the Appendix 4 tables
I₂Current ensuring effective operation of the device1.45 × In for a circuit breaker · must not exceed 1.45 × Iz
IaCurrent causing automatic operation in time5 × In for a type B
≤The chain that ties them together: Ib ≤ In ≤ Iz, where Iz = It × the factors — so you need It ≥ In ÷ the factors. Get that order straight and most cable-design questions unlock.

Part 2 · symbols (pp.52–53) and abbreviated terms (pp.54–55), at the end of the part

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside