The split-load boardHow many neutral bars on a split-load board?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

A split-load board shares RCDs between groups of circuit breakers. Ours is a 10-way board with the same main switch as before, plus two RCDs:

  • Both RCDs are 30 mA, Type A (the sine wave plus pulsating-DC symbol), and each is rated as an 80 A isolator: it can switch 80 A through. (The main switch carries 100 A.)
  • The RCDs can be slid along the rail to space the board out.
  • The busbars come loose in the box: two with 4 spines and one with 5. Read the manufacturer's instructions before cutting any down to suit. If they say don't, doing it voids the warranty.
  • Plastic busbar end covers are included to go over unused spines. Leave the plastic sleeve on the busbar itself.
  • The thick cables between the main switch and the RCDs come pre-fitted from the factory.
N bar 3 (RCD 2) N bar 2 (RCD 1) N bar 1 RCD 230 mA RCD 130 mA tails from main switch main 4 CBs on RCD 2 4 CBs on RCD 1 earth bar: all CPCs 3 separate neutral bars not joined to each other Each circuit's neutral goes in the bar that belongs to the RCD protecting it. Ways 1–2 (tinted orange) are the unprotected side: no RCD.
Redrawn split-load layout. Anything between the main switch and RCD 1 is on the unprotected side and uses neutral bar 1. Circuits on RCD 1 use neutral bar 2, and circuits on RCD 2 use neutral bar 3. The easy check: each RCD has a short cable running up to its own neutral bar.

How it's fed

  • Two brown tails leave the bottom of the main switch: one to the top of each RCD. So both RCDs are fed directly from the main switch, and turning the main switch off turns everything off.
  • On the neutral side, one cable goes from the main switch to a neutral bar, and another goes to the RCDs. Each RCD's neutral out goes up to its own neutral bar.
  • The loose busbars fit into the line terminal at the bottom of each RCD. Then the CBs drop onto the spines and hook onto the DIN rail.
  • A circuit is just line joined to neutral through a load. Line comes from the RCD's busbar through the CB. Neutral must go back to that same RCD's neutral bar.
The golden rule of split-load boards
There are three separate neutral bars, isolated from each other, but one shared earth bar for all CPCs. Put every circuit's neutral in the bar that belongs to the RCD protecting it. Get it wrong and you'll get tripping (see section 11).

The unprotected side

Our example: an SWA (steel wire armoured) cable out to a garage or shed, with its own small consumer unit there.

  • The circuits in the shed may well need RCD protection, so you fit RCBOs in the shed board.
  • If the shed's feed cable were on RCD 1 in the house, a bit of damp in the shed could trip RCD 1 and knock off every circuit in the house on that side. That isn't against the rules, just frustrating.
  • So you might decide the distribution circuit from house to shed doesn't need an RCD (the SWA has an earthed metallic covering), and put its CB on the unprotected side, between the main switch and RCD 1. Its neutral goes in neutral bar 1.

RCBOs on a split-load board

  • An RCBO can go on the unprotected side. Its fly lead goes into neutral bar 1, and the circuit's line and neutral go into the RCBO.
  • Never put an RCBO under an RCD. That puts two 30 mA RCDs in series and they end up in conflict: an earth fault on that circuit might trip the RCD as well as, or instead of, the RCBO, depending on which one is slightly more sensitive from the factory. You lose selectivity and waste the money you spent on the RCBO.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside