The Rn + R2 alternative: proving conductors are in the RIGHT placeWhen do you test Rn plus R2?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Guidance Note 3 · p.59 · Figure 2.14. An alternative to test method 1 (R1 + R2), for protective conductors downstream of a control device that is open-circuit when power is removed — contactors, motion or day/night controls, timers, dimmers, smart switches, building management systems.
The neutral is not switched, so you link neutral to earth temporarily at the board and measure Rn + R2 at each point. It proves the cpc the same way, through the neutral instead of the line.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk