Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Guidance Note 3 · 2.6.18 · p.95. The book has you press the RCD's own test button before you use the test instrument — and the earth fault loop impedance is tested before the RCD tests.

Practice on site: press it before you test, carry out the RCD tests, then press it again afterwards to confirm the device is still functioning. Twice.
✋If the button does not trip it, stop. The device has failed and is replaced — there is no point carrying on with the RCD tests. Testing manually rather than on auto lets you run half times and one times without the optional five times test.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside