The eleven steps of cable selection

From a kilowatt rating to a verified cable, CPC and protective device. Most people stop around step 7, at volt drop — which is halfway.

StepFindWhere
1Ib — design currentP ÷ V
2In — device ratingTable 41.3 / B6 / A6
3Reference methodBS 7671 Appendix 4, Table 4A2
4Correction factorsAppendix 4 — Ca, Cg, Ci, Cf
5It needed — required capacityIn ÷ the factors
6It — tabulated capacity → cable sizeTable 4D5 for twin and earth
7Volt dropSame table — mV/A/m
8Expected R1+R2GN3 Appendix B / OSG Appendix I
9Zs, checked against the maximumZe + (R1+R2)
10IpfU0 × Cmin ÷ Zs
11CPC size — adiabaticBS 7671 Chapter 54
The worked example that follows: a 9 kW shower, 25 m of twin and earth, ambient 35 °C, run over the joists in a ceiling under thermal insulation, protected by an RCBO. Ze given as 0.21 Ω.
From a kilowatt rating to a verified cable, cpc and device 1Ib — design current P ÷ V 2Iₙ — device rating Table 41.3 / B6 3reference method Table 4A2 4correction factors Cₐ Cg Cᵢ Cf 5It needed — required capacity Iₙ ÷ the factors 6cable size Table 4D5 7volt drop mV/A/m most people stop here — which is halfway 8expected R₁ + R₂ GN3 App B 9Zₛ, checked against the maximum 10Ipf — Uₒ × Cmin ÷ Zₛ 11cpc size — adiabatic BS 7671 Chapter 54 the worked example 9 kW shower · 25 m twin and earth ambient 35 °C · in insulation Ib 39.13 A → 40 A device → 10 mm² → volt drop 4.3 V → Zₛ 0.40 Ω → cpc 1.5 mm² minimum
Steps 1 to 7 size the cable. Steps 8 to 11 prove it will actually disconnect in time and that the cpc will survive the fault — which is the part that makes it a design rather than a guess.

Step 1 — design current

Ib = P ÷ V = 9000 ÷ 230 = 39.13 A

Step 2 — In, and whether diversity applies

In = 40 A Type B RCBO

Check Table A2 before assuming diversity. For an instantaneous water heater or shower, the entry is either 100% of the largest appliance or no diversity allowed — so either way, the full 39.13 A stands. Nothing to reduce.

A cooker would be different. That is where the Table A1/A2 arithmetic earlier comes in. A shower does not get it.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside