The appendices worth tabbingWhich appendix holds the time-current curves?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
The contents list 17 appendices, but Appendix 7 and Appendix 17 are listed as deleted and Appendix 12 as not used, so 14 have content. Realistically five of them earn a tab. A quick tour of them:
Appendix 1 — British Standards
The list of BS and other standards referenced by the book. It is the one to read if you want to fall asleep. Know it exists; don't study it.
Appendix 2 — three pages, one useful table
Appendix 2 runs pp.434–436 — statutory regulations and associated memoranda. The only thing in it worth highlighting is the table at the very end, on p.436:
Nominal voltage and its permitted tolerance
Nominal voltage to earth, U₀ = 230 V Permitted tolerance = +10 % / −6 % 230 − 6 % = 216 V 230 + 10 % = 253 V In force since 1 January 1995
This answers a question raised earlier: can the supply coming into a property be more or less than 230 V? Yes — legitimately anywhere between 216 V and 253 V.
Appendix 3 — time/current characteristics
- Where you get your fault currents and disconnection times for overcurrent devices. You've now been in it repeatedly across these modules.
- Appendix 3 prints, with each set of curves, a table giving the current needed to operate the device within 0.1 s and within 5 s. That is where the t in the adiabatic equation comes from: the device's operating time, read from Appendix 3.
- The curved part of the characteristic is overload protection; the straight part is the high fault current giving you the 0.1 s or 0.4 s trip.
- Worked from it: a BS 88-2, 80 A fuse needs 750 A to operate in 0.4 s. Find the 0.4 s column and read the current: 750 A.
Appendix 4 — current-carrying capacity and circuit design
Enormous, and the one you'll live in during cable calculation work. Everything below sits in it.
| Symbol | What it is |
|---|---|
| CA | Ambient temperature — the air temperature around the cable |
| CI | Thermal insulation around the cable |
| CG | Grouping — the number of cables or circuits grouped on the same run |
| CC | Cable buried in the ground (in a duct or direct) — 0.9 |
| CF | The BS 3036 semi-enclosed fuse factor — 0.725 |
| I₂ | The operating current including the fusing factor, for operation within the conventional time after a device protecting against overload |
| Ib · In · Iz | All defined here as well as in Part 2 — and the formula for the tabulated rating you need: It ≥ In ÷ the rating factors |
Also in Appendix 4, and worth its own tab:
- Table 4Ab — voltage drop limits: 3 % for lighting, 5 % for everything else. At 230 V that's 6.9 V and 11.5 V. You won't have the On-Site Guide in the exam, so this is where you get them. Expect the question to want the volts, not the percentage.
- Table 4B1 — ambient temperature rating factors. Example: 70 °C thermoplastic at a 40 °C ambient gives CA = 0.87.
- Installation reference methods — how cables may be installed and what's permitted, including reference method 100.
- The triple harmonics table, if a question ever asks about harmonic content in particular cable types.
- The Iz ≥ In formulas, several versions for different circumstances.
Appendix 5 — external influences
Any question about an external influence: Appendix 5 first, Chapter 52 second. Codes worth knowing:
- AG = impact. AG1 = low severity — normal household and similar equipment.
- AE = presence of foreign solid bodies — the IP-rating end of things.
- BA4 = instructed person, BA5 = skilled person.
- Temperature is an external influence too — which is why the sauna question is really an external-influence question.
Appendix 1 · British Standards Appendix 2 · p.436 · 230 V nominal · +10 % / −6 % · 216–253 V ★ Appendix 3 · time/current characteristics · BS 88-2 80 A at 0.4 s = 750 A Appendix 4 · CA CI CG CF · Ib In Iz I₂ ★ Table 4Ab · voltage drop 3 % / 5 % ★ Table 4B1 · ambient temperature · 40 °C = 0.87 Appendix 5 · external influences · AG1, AE, BA4, BA5 ★
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing