The adiabatic equation, and when to use itWill the CPC survive the fault?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
What it's for: the final calculation. It checks whether the CPC can carry the prospective fault current for as long as the device takes to operate. In an earth fault you might have several hundred amps in the CPC. It's a piece of copper, and it can't carry unlimited current. At some point it would melt, and that could cause a fire. After, say, 0.4 s the fuse blows and everything "chills out". The question is whether the CPC survives until then.
What is k?
k covers the thermal constraints of the conductor under fault current: its material, its insulation and how warm it already is. Some analogies:
- Running up a hill: someone in their mid-50s, a few extra pounds, not feeling their best, will take a while. Twenty years younger, they'd have scarpered up it. Same hill, different constraints.
- A CPC in twin and earth is nestled between a line and a neutral, both "cooking away" with current, so it's already warm. A CPC formed by the steel wire armour of an SWA sits round the outside in fresh air with nothing heating it. Different constraints, so different k.
- A huge plate of food: "I only ate an hour ago, I can't fit any more in." It depends on the constraints of your belly at the time.
Use Chapter 54. It gives a far wider range of k values for protective conductors. k also appears in Table 43.1, but that's for a different calculation, so don't use it for earth faults.
For a CPC in 70 °C thermoplastic twin and earth (copper), Table 54.3 gives k = 115. Underneath, it asks whether the conductor is bigger than 300 mm². If yes, use 103. A 1.5 mm² CPC is much smaller than that, so it's 115.
BS 7671 · Chapter 54 · values of k for protective conductors BS 7671 · Table 54.3 · 70 °C thermoplastic, copper: k = 115 (103 above 300 mm²)
A hypothetical: you do the sum and get 1.3 mm². You've got a 1.5 mm² CPC, so "I'm all right". Here's a full numbers example using the fuse values above.
Another example: 20 A BS 3036 fuse, 1.5 mm² T&E CPC
I = 130 A (just enough for 0.4 s, from the table above) t = 0.4 s k = 115 (Table 54.3, 70 °C thermoplastic, copper) S = √(I² × t) ÷ k = √(130² × 0.4) ÷ 115 = √(16 900 × 0.4) ÷ 115 = √6760 ÷ 115 = 82.22 ÷ 115 = 0.71 mm² (minimum) 1.5 mm² CPC ≥ 0.71 mm² ✓ the CPC survives until the fuse blows
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing