The 80 % rule and the On-Site GuideWhy multiply the table value by 0.8?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

The values in BS 7671 are for a circuit in use — a cable at its operating temperature of 70 °C. Current through copper makes it hot, and hot copper has more resistance. So a circuit that's been running has a higher Zs than the same circuit stone cold.

%When you test a brand new, unenergised circuit, it's cold. Its measured Zs should therefore be no more than 80 % of the tabulated value, leaving 20 % of headroom for the warming-up it will do in service.
DeviceBS 7671 tabulated (100 %)Max measured (80 %)
Type B 50 A0.87 Ω0.70 Ω (0.87 × 0.8)
Type B 16 A2.73 Ω2.19 Ω (On-Site Guide, Table B6)
You don't have to do the sum. The On-Site Guide already prints the 80 % figures — Appendix B, Table B6 for circuit breakers. Look up type B, 16 A and it gives 2.19 Ω directly (2.73 × 0.8 on the rounded table figure comes to 2.18). That's the number you're checking against with your tester in your hand.
!Which book, which number.
BS 7671 tables = maximum permitted Zs, circuit in use, 100 %.
On-Site Guide tables = maximum measured Zs, new circuit, 80 %.

Spotting which one a question wants

The book uses several phrasings and they are not interchangeable:

Wording in the questionUse
maximum tabulated / permitted / allowed / acceptableThe BS 7671 value, 100 %
maximum measuredThe 80 % value — multiply by 0.8

Worked example: "A 32 A BS EN 60898 type C circuit breaker… what is the maximum acceptable measured Zs?" → Table 41.3 gives 0.68 Ω → the word "measured" means multiply by 0.8, or read the type C, 32 A figure from OSG Table B6. The wrong answer 0.68 is sitting right there in the options for anyone who missed the word "measured".

On-Site Guide · Appendix B · Table B6 · 80 % Zs for circuit breakers Table 41.3 · 100 % tabulated values

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside