Table A1, and the cooker worked throughWhy add five amps for a cooker socket?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Table A1 — assumed demand
Everything starts with the design current, from the power triangle:
Same formula you already know as I = P/V. In a design it is called Ib, the design current.
Table A1 then tells you what to assume for each kind of point. For a household cooker the sum is the one On-Site Guide · Table A2 · p.151 prints: 10 A, plus 30% of the full load in excess of 10 A, plus 5 A if a socket-outlet is built into the control unit. Table A1 gives the same result.
The cooker, worked through
A 5.5 kW cooker on a 230 V supply, with a socket outlet in the control unit.
| Step | Working | Result |
|---|---|---|
| Design current | 5500 ÷ 230 | 23.91 A |
| Take the first 10 A | 23.91 − 10 | 13.91 A |
| 30% of the load in excess of 10 A | 13.91 × 0.3 | 4.17 A |
| Add the 10 A back | 10 + 4.17 | 14.17 A |
| Socket in the control unit | + 5 | 19.17 A |
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing