Supply polarity, three phase: ten readingsWhich readings should be 400 volts?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Same idea, more combinations. Between any line and neutral, or any line and earth, it’s 230 V. Between two lines, 400 V. Neutral to earth, zero.

ReadingsExpect
N – L1 · N – L2 · N – L3230 V each
E – L1 · E – L2 · E – L3230 V each
N – E0 V
L1 – L2 · L1 – L3 · L2 – L3400 V each

Any other combination is incorrect supply polarity, and the same rule applies: stop.