Supply polarity, three phase: ten readingsWhich readings should be 400 volts?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Same idea, more combinations. Between any line and neutral, or any line and earth, it’s 230 V. Between two lines, 400 V. Neutral to earth, zero.
| Readings | Expect |
|---|---|
| N – L1 · N – L2 · N – L3 | 230 V each |
| E – L1 · E – L2 · E – L3 | 230 V each |
| N – E | 0 V |
| L1 – L2 · L1 – L3 · L2 – L3 | 400 V each |
Any other combination is incorrect supply polarity, and the same rule applies: stop.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk