Free notes
Supplementary bonding in bathrooms, and when you can avoid itWhen can you leave out bathroom bonding?
Free from the notes: the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Unlike main bonding, supplementary bonding can often be avoided. The classic example is a bathroom, meaning any room containing a bath or shower. The fan, light and shaver point are often on the lighting circuit, joined by its CPC back to the MET. The bath taps, radiator and sink taps are on copper pipes that connect to the main water and gas, which should have main bonding downstairs.
Why a bathroom is an area of increased risk
- It's usually a small, confined space, full of things connected to extraneous conductive parts: taps, radiators, baths, shower trays and towel rails.
- People are likely to be undressed, so more skin is exposed and there's more chance of touching, say, a radiator.
- Skin is likely to be wet, so body resistance is much lower.
Imagine an earth fault at the shaver point. Even with main bonding in place, a person touching the shaver point and a tap could still see a potential difference, and they're in a much riskier situation.
- All final circuits in the location meet the required disconnection times for ADS.
- All final circuits in the location have additional protection by a 30 mA RCD.
- All extraneous conductive parts in the location are effectively connected to the main protective bonding.
One way to check the third condition: the resistance between the MET and each extraneous conductive part is less than 1667 Ω. Measure it with a low-resistance ohmmeter using the wander (long) lead, test method 2.
Where 1667 Ω comes from
R ≤ 50 V ÷ IΔn (Reg 415.2.2), the same 50 V figure as Table 41.5 (Zs × IΔn ≤ 50 V) 30 mA RCD: 50 ÷ 0.03 = 1667 Ω → no more than 50 V (the touch voltage limit) can appear between a faulty exposed part and an extraneous part before the RCD disconnects.
The 1667 Ω figure (R ≤ 50 V ÷ IΔn) is a way of checking the third condition, not a condition of its own.
BS 7671 · Reg 701.415.2 supplementary bonding · p.258 (Section 701 starts p.257) BS 7671 · Table 41.5 max earth fault loop impedance for RCDs (30 mA → 1667 Ω) · p.77
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing