Supplementary bonding in bathroomsDoes every bathroom still need supplementary bonding?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Supplementary bonding links exposed and extraneous conductive parts locally, e.g. the metal pipes under a bath to a metal shower, so they stay at the same potential. You'll often see it as a loop of green/yellow between copper pipes, such as at a boiler. Somewhere along those pipes, a main bonding conductor goes back to the MET.

electric shower bath basin light electrictowel rail supplementary bonding (green/yellow) shower ↔ bath pipes ↔ basin pipes ↔ towel rail
Supplementary bonding is a real pain to install, because every metal pipe connection needs linking. It's rarely installed now, because it can be left out when the three conditions below are met.
Supplementary bonding may be omitted in a room with a bath or shower (BS 7671 701.415.2) if all three are met:
  1. All final circuits in the location meet automatic disconnection of supply (ADS): a CB within the Table 41.1 time (0.4 s TN, 0.2 s TT), a 30 mA RCD within 300 ms.
  2. All final circuits in the location have additional protection by a 30 mA RCD.
  3. All extraneous conductive parts are effectively connected to the main protective bonding (back to the MET).

BS 7671 · Section 701: locations containing a bath or shower — starts p.257 BS 7671 · Reg 701.415.2 supplementary bonding, and when it may be omitted · p.258

Supplementary bonding conductor sizes

This depends on what you're linking and whether the conductor is mechanically protected, e.g. in conduit. A single-core green/yellow conductor has only one layer of insulation. The grey sheath on twin and earth is mechanical protection, and an RCD is additional protection, not mechanical.

Worked example

CPC of the circuit feeding the exposed part = 10 mm²
Link: electric shower (exposed part) → pipes under the bath (extraneous part)
Not mechanically protected → 6 mm² (still 6 mm² if protected)
Exposed part → exposed part, both mechanically protected with 10 mm² → 10 mm²

Electrician's Guide to the Building Regs · 3.3.3 Supplementary bonding conductors · Table 3.3.3 sizes · p.62

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside