Fused spur
A branch taken from the ring through a fused connection unit (FCU).
  • The number of fused spurs is unlimited.
  • The FCU fuse is 13 A maximum (it can be 3 A or 5 A), so the cable after it can be smaller, e.g. 1.5 mm² to a light or a shed.
  • It can feed fixed equipment such as a hand dryer, a towel rail or an unswitched appliance socket.
Unfused spur
A branch taken straight from a socket (or a junction box) with no fuse.
  • The cable must be the same size as the ring (2.5 mm²).
  • The number of unfused spurs must not exceed the number of socket-outlets on the ring.
  • Only one spur from each socket, and you can't spur off a spur.

On-Site Guide · Appendix H · H2.4 Spurs (fused unlimited, unfused ≤ number of sockets) · p.219

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside