Socket circuits: rings and radialsWhat's the difference between a ring and a radial?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
| Circuit | Protective device | Min. copper CSA (T&E) | Max. floor area |
|---|---|---|---|
| Ring final | 30 or 32 A | 2.5 mm² | 100 m² |
| Radial | 20 A | 2.5 mm² | 50 m² |
| Radial | 30 or 32 A | 4.0 mm² | 75 m² |
- This table is for normal socket-outlet circuits. Lighting (usually 6 A), cookers, showers and immersion heaters go through the full design process instead.
- Floor area means the room area served, not metres of cable. On a 20 A radial, 50.02 m² is already too much.
- Many kitchens now use a 32 A radial in 4 mm² instead of a ring. Rings go on a 32 A device. If you need smaller breakers, use two 20 A radials instead.
Electrician's Guide to the Building Regs · 4.2 Final circuits using 13 A socket-outlets · Table 4.2.1 · p.77 On-Site Guide · Appendix H · Table H2.1: final circuits using socket-outlets · p.218 Worth highlighting
On-Site Guide · Appendix A: maximum demand · p.149
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing