Exactly as they are on the site.
Earlier the adiabatic equation was used to find t — how long a cable survives a given fault current. Here it's rearranged to find S — the minimum size the protective conductor has to be. Same four letters, different unknown.
t = k²S² ÷ I²
How long before the cable is destroyed?
S = √(I²t) ÷ k
What's the smallest CPC that survives?
- S
- The nominal cross-sectional area of the conductor, in mm². CSA means the copper only — never the copper plus its insulation.
- I
- The fault current, in amperes.
- t
- The operating time of the protective device, in seconds — from Appendix 3.
- k
- A factor for the conductor and its insulation. Not the k you used in Chapter 43 earlier — these k values come from the Tables 54.2 onward.
The worked example: is the CPC in 2.5 mm² twin & earth big enough?
The scenario, word for word:
- Find I. Type B trips at 5 × In — the worst case of the 3–5 range. 5 × 20 = 100 A. You could look it up in Appendix 3 instead of calculating it; you get the same number.
- Find t. In Appendix 3, Figure 3A4 (type B) gives the current needed to operate the device within 0.1 s and within 5 s. For a 20 A type B that is 100 A, so at 100 A it operates within 0.1 s: t = 0.1 s — well inside the 0.4 s a TN final circuit needs.
- Find k. Go to the tables from 54.2 onward and pick the right one. Twin & earth is a multicore sheathed cable with the protective conductor incorporated in it, at an assumed initial temperature of 70 °C or greater, copper — so k = 115.
Proving the 1.5 mm² CPC is big enough
S = √(100² × 0.1) ÷ 115 S = √(10 000 × 0.1) ÷ 115 S = √1000 ÷ 115 S = 31.62 ÷ 115 S = 0.27 mm² minimum Actual CPC in the cable = 1.5 mm² 1.5 mm² ≥ 0.27 mm² → adequate
Why the k tables don't say "twin & earth"
A fair question: why isn't there a row that just says twin & earth, the way the cable tables do? Because you might be looking for the CPC inside any multicore sheathed cable — a three-core-and-earth, for instance — and the table has to cover all of them. Read the description, not the cable name.
Chapter 54 · cross-sectional area of protective conductors · the S formula ★ Tables 54.2 onward · p.210 · k values · copper in a sheathed cable = 115 ★ Appendix 3 · Figure 3A4 · type B · currents for 0.1 s and 5 s ★ 434.5 · the adiabatic (Part 4, Part 1)
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing