Sizing a CPC — the adiabatic, rearrangedHow small can a protective conductor be?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Earlier the adiabatic equation was used to find t — how long a cable survives a given fault current. Here it's rearranged to find S — the minimum size the protective conductor has to be. Same four letters, different unknown.

D1Earlier
t = k²S² ÷ I²
How long before the cable is destroyed?
D2Here
S = √(I²t) ÷ k
What's the smallest CPC that survives?
S
The nominal cross-sectional area of the conductor, in mm². CSA means the copper only — never the copper plus its insulation.
I
The fault current, in amperes.
t
The operating time of the protective device, in seconds — from Appendix 3.
k
A factor for the conductor and its insulation. Not the k you used in Chapter 43 earlier — these k values come from the Tables 54.2 onward.

The worked example: is the CPC in 2.5 mm² twin & earth big enough?

The scenario, word for word:

?2.5 mm² / 1.5 mm² flat twin & earth, 70 °C thermoplastic, on a BS EN 60898 type B 20 A circuit breaker. Prove the 1.5 mm² CPC has been sized correctly.
  1. Find I. Type B trips at 5 × In — the worst case of the 3–5 range. 5 × 20 = 100 A. You could look it up in Appendix 3 instead of calculating it; you get the same number.
  2. Find t. In Appendix 3, Figure 3A4 (type B) gives the current needed to operate the device within 0.1 s and within 5 s. For a 20 A type B that is 100 A, so at 100 A it operates within 0.1 s: t = 0.1 s — well inside the 0.4 s a TN final circuit needs.
  3. Find k. Go to the tables from 54.2 onward and pick the right one. Twin & earth is a multicore sheathed cable with the protective conductor incorporated in it, at an assumed initial temperature of 70 °C or greater, copper — so k = 115.

Proving the 1.5 mm² CPC is big enough

S = √(100² × 0.1) ÷ 115
S = √(10 000 × 0.1) ÷ 115
S = √1000 ÷ 115
S = 31.62 ÷ 115
S = 0.27 mm² minimum

Actual CPC in the cable = 1.5 mm²
1.5 mm² ≥ 0.27 mm² → adequate
✋Only I²t goes under the square root. It is easy to get wrong by rooting the whole fraction, k included. Do it in parts, or bracket the numerator. On a fraction-style calculator: fraction button, square root inside the top, 100 squared × 0.1, then 115 on the bottom, equals, then convert out of fraction form.
✋You may NOT use the adiabatic to size a bonding conductor. Worth marking clearly in your own notes — it is a common trap. A main protective bonding conductor — your 10 mm² to the gas and water, say — is sized from specific regulations and tables based on the incoming live conductors, never from the adiabatic. Getting this backwards is a classic exam trap.

Why the k tables don't say "twin & earth"

A fair question: why isn't there a row that just says twin & earth, the way the cable tables do? Because you might be looking for the CPC inside any multicore sheathed cable — a three-core-and-earth, for instance — and the table has to cover all of them. Read the description, not the cable name.

Watch the sheath-or-armour row. One row covers cables where the sheath or armour is itself the protective conductor — SWA, for instance. In twin & earth the CPC is a separate bare conductor, not the sheath, so that row is not yours. This is where most people pick the wrong table.
115 and 103. Both appear, and the difference is the final temperature the conductor is permitted to reach before the cable is destroyed. For 70 °C thermoplastic copper under 300 mm², it's 115.
Tab this. Worth tabbing the k tables with their printed table number, such as "Table 54.2". Legal, because the tab only carries what's printed on that page.

Chapter 54 · cross-sectional area of protective conductors · the S formula ★ Tables 54.2 onward · p.210 · k values · copper in a sheathed cable = 115 ★ Appendix 3 · Figure 3A4 · type B · currents for 0.1 s and 5 s ★ 434.5 · the adiabatic (Part 4, Part 1)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside