Safe zones, depth and metal stud wallsWhere can a cable run in a wall without extra protection?

Free from the notes: the section word for word as members see it, and a PDF to keep.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
✗ diagonal run: outside the zones socket switch 150 mm below ceiling 150 mmat corners Green = permitted zones: in line (vertically or horizontally) with an accessory, within 150 mm of the ceiling, or within 150 mm of a corner.

Cables concealed in a wall less than 50 mm deep must be protected in one of these ways:

  1. An earthed metallic covering, or enclosed in earthed metal conduit, trunking or ducting.
  2. Mechanical protection against penetration by nails and screws.
  3. Run in the permitted zones. This also needs 30 mA RCD additional protection.
  4. Part of a SELV/PELV circuit (extra-low voltage, covered later).
  • Why the zones? Nobody is likely to hang a picture 150 mm from the ceiling or right in a corner. Cables in line with an accessory are where people expect them.
  • Running across into a different room through a partition isn't "in line with an accessory", so it needs extra protection.
  • Metal or plastic capping over cables in a chase is good practice, because it stops nails and screws. Capping doesn't count as conduit or trunking.
  • Under floors and in ceilings: unarmoured cables through joists must be at least 50 mm from the top or bottom of the joist, or be protected (earthed steel conduit, etc.). This is Reg 522.6.201. Where an old, thin joist can't give 50 mm top and bottom, the cable must meet 522.6.204 instead.

Electrician's Guide to the Building Regs · Permitted cable routes / safe zones figure and <50 mm depth rules · p.43

Metal stud walls: Reg 522.6.203
If a circuit is installed in a stud wall made mainly of metal, a 30 mA RCD is required, unless Reg 522.6.204 is followed. That means the cable has an earthed metallic covering, is in earthed conduit or trunking, has mechanical protection against penetration, or is part of SELV/PELV.
The RCD doesn't stop the cable being damaged. It protects the person from a shock if a screw or nail goes through it.

BS 7671 · Reg 522.6.201: cables through joists · p.151 BS 7671 · Regs 522.6.202, 522.6.203, 522.6.204: cables in walls and metal stud partitions · p.152 In the 18th Edition exam you find regs by number, not page. Practise.

Resistance, length and size
Resistance is directly proportional to length: double the length, double the resistance. It's inversely proportional to CSA: a bigger cable has lower resistance. Going from 4 mm² to 10 mm² (2.5× bigger) cuts resistance by 2.5×. Adding cable to a circuit raises its resistance, so test readings change.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside