Safe isolation comes first

Before any testing, the installation or the part of it you are working on is isolated and proved dead. The reason is legal as much as practical.

RegulationWhat it does
EAWR · Reg 4Systems to be constructed and maintained to prevent danger, so far as is reasonably practicable
EAWR · Reg 4(3)Maintenance work itself to be carried out in a manner that prevents danger
EAWR · Reg 14Live working — the three conditions, all of which must be met
EAWR · Reg 29The defence: having taken all reasonable steps and exercised all due diligence

Regulation 14's three conditions, all of which must be satisfied before live working is justified:

1It is unreasonable in all the circumstances for the conductor to be dead
2It is reasonable in all the circumstances to be at work on or near it while live
3Suitable precautions are taken to prevent injury — including, where necessary, suitable protective equipment
✋A glove is not a licence. Protective equipment for live work means heavy insulated gauntlets running well up the forearm, not thin rubber gloves — and it protects the part of you it covers, nothing else. Enough fault current will burn through it.

Can a periodic be done entirely dead?

No — and it is worth understanding exactly why, because it is the clearest everyday use of Regulation 14.

Live testCould it be avoided?How
ZeYesCan be enquired of the DNO
ZsYesCan be calculated — Ze + (R1+R2)
IpfYesCan be enquired or calculated
RCD testNoThere is no way to prove a trip time on a dead circuit
The RCD test is the one live test you cannot design your way out of

An RCD operates on an imbalance of current between line and neutral, not on potential difference. There has to be current flowing for there to be an imbalance to detect — so the circuit has to be live and complete. Test at the furthest outlet where practicable.

So the RCD test is the one live test that cannot be avoided, which is how condition 1 of Regulation 14 is satisfied for it.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside