Ring final testing: rings onlyShould a lighting circuit ever be a ring?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
This test is only done where there is a ring final — and rings are for socket-outlet circuits. Lighting and cookers are radials. If you meet a lighting circuit wired as a ring, it’s not a standard circuit, and it’s worth asking why.
The ring came in after the war, when a great many homes were being built and copper was short: one 2.5 mm² circuit, out and back, on a 30 or 32 A device. It’s still installed every day, and there are millions of them in service, so you will test them.
It’s a dead test, so the circuit is isolated, and it uses the low-resistance ohmmeter. Disconnect all six conductors of the ring at the board: both lines, both neutrals, both CPCs. (On an RCBO, the neutrals come out of the RCBO.)
Guidance Note 3 · 2.6.6 · continuity of ring final circuit conductors · from p.63 On-Site Guide · Appendix H · Table H2.1 · standard socket circuits
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing