Reading the BS 7671 cable tablesWhat must the table rating reach?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: What must the table rating reach? The answer is in the notes below.
The notes
Exactly as they are on the site.
What it's for: finding a cable size whose current rating covers your It. Once you know It, you go to the right cable table for your cable type and read down the column for your installation method.
- The cable tables ("current-carrying capacity" tables) fill over 40 pages of Appendix 4. The top-right corner of each says copper or aluminium; the aluminium tables start with Table 4H1A.
- Tables ending in A hold the current ratings. The matching B table on the next page holds the voltage drop (mV/A/m). That's why you skip every other page as you search.
- The one exception is Table 4D5 (flat twin and earth, p.484). It fits ratings and volt drop on a single table.
| Table | Cable |
|---|---|
| 4D1A | Single-core 70 °C thermoplastic (not ours) |
| 4D2A | Multicore 70 °C thermoplastic (not ours) |
| 4D3A | Single-core armoured 70 °C thermoplastic (not ours) |
| 4D4A / 4D4B | Multicore armoured 70 °C: ratings / mV/A/m (not ours) |
| 4D5 | 70 °C flat twin and earth, ratings and mV/A/m on one table, p.484 (not ours) |
| 4E1A | Single-core 90 °C thermosetting, non-sheathed: our cable |
| 4E1B | Its voltage drop (mV/A/m) table |
BS 7671 · Appendix 4 · cable tables · copper first, then aluminium (from Table 4H1A) BS 7671 · Table 4E1A · 90 °C thermosetting single-core, current ratings · p.486 BS 7671 · Table 4D5 flat T&E · p.484
Worked example: choosing the cable
Table 4E1A · first column = conductor CSA (mm²) Use the Reference Method B, single-phase (2 cables) column Read down it for the first value ≥ 20.83 A: 1.5 mm² → 23 A ✓ → 1.5 mm² 90 °C thermosetting singles, in conduit (Method B), can carry up to and including 23 A.
In summary: know In, the cable type, the installation method and the correction factors. Do the It calculation. Then find a table value that's bigger.
It ≥ In ÷ (factors) = 20.83 A is the smallest tabulated current-carrying capacity you can accept, so you pick the first table value that's bigger: 23 A. Iz is the cable's rating once the factors are applied: 23 × 0.96 × 0.8 = 17.66 A, which is ≥ In (16 A) ✓.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing