RCMs, AFDDs and fuse standardsWhat's the difference between an RCD and an RCM?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The question at the end: What's the difference between an RCD and an RCM? The answer is in the notes below.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

532 — devices for protection against fire

§Where required by Chapter 42, an RCD with a rating not exceeding 300 mA shall be installed at the origin of the circuit to be protected.

Residual current monitors

An RCM monitors residual current and warns, rather than disconnecting. That matters where cutting the supply would be worse than the fault itself.

Where you'd actually use one: data centres, where dropping the network is unacceptable, and life-safety systems. Also associated with IT systems — a high-impedance earthing arrangement you're unlikely to meet in domestic work.

Testing: BS 7671 requires an RCD to be tested at one times its rated residual current, and Guidance Note 3 recommends a half times test as well, where it should not trip — so 15 mA and 30 mA for a standard 30 mA device (Guidance Note 3 · Table 2.18(a) · p.96).

AFDDs, again

Arc fault detection devices appear here as fire-protection devices, having already appeared in 421.1.7 earlier. They shall be installed at the origin of the final circuit to be protected, on single-phase AC final circuits supplying socket-outlets not exceeding 32 A, in higher-risk residential buildings, HMOs, purpose-built student accommodation and care homes.

What an arc actually is: a plug not pushed fully home can arc between the live contacts. AFDDs are designed to catch exactly these small domestic arcs, not just dramatic ones.

Fuse standards worth recognising

StandardWhat it is
BS 88Cartridge fuse — including the supplier's cut-out fuse
BS 1362The plug-top fuse
BS 3036Semi-enclosed rewireable fuse — the 0.725 factor
BS 646Small ceramic cartridge fuse, similar in appearance to a plug-top fuse

532 · devices for protection against fire · RCD ≤ 300 mA 532.3 · p.168 · residual current monitors 421.1.7 · AFDDs (Part 4)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside