There are now lots of different types of RCD. Chapter 53 sets them out in detail, at Regulation 531.3.3.

  • Type AC only detects AC (sine-wave) residual currents.
  • Type A adds pulsating DC, Type F adds mixed-frequency currents, and only Type B detects smooth DC.
  • The limits in 531.3.3: a Type A still works with smooth DC up to 6 mA, a Type F up to 10 mA, and a Type B up to 0.4 × IΔn or 10 mA, whichever is higher.

A Type AC should only be installed where it's known that the load contains no DC components. In modern life, there are very few times you could fit a Type AC.

So the focus is now on Types A, F and B:

  • Type A is the most common. It meets the minimum requirement and is the "one size fits all".
  • Types F and B are for more specific jobs, often seen with things like EV charging.

BS 7671 · Chapter 53 · Reg 531.3.3 · RCD types · Type AC only where the load has no DC components · pp.165–166

residual current waveform Type ACType AType FType B AC (sine wave) pulsating DC mixed frequency smooth DC ✓✓✓✓ –✓✓✓ ––✓✓ –––✓
Our summary of the types. Each type detects everything the one to its left does, plus more. Types A and F cope with small amounts of smooth DC (up to 6 mA and 10 mA), but only Type B is designed to detect smooth DC fully.
Watch out: "A, B and F detect DC"
Only Type B detects smooth DC residual current. Type A detects AC plus pulsating DC. Type F adds mixed-frequency currents (such as from inverter-driven equipment). A large smooth DC current can stop a Type A or F from working properly. That's why EV charge points (Section 722) need a Type B, or a Type A or F with a separate 6 mA DC detection device.

Sparky's closing advice: be clear on when an RCD has to be installed and which job it's doing, and use the regs to your advantage.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside