The second job is fault protection. An RCD is used for fault protection in two situations:

  1. The installation is part of a TT system.
  2. The circuit's disconnection time is longer than the maximum allowed.

Both are covered in Section 411 (automatic disconnection of supply).

BS 7671 · Section 411 · automatic disconnection of supply (TT systems and maximum disconnection times)

Most circuits have a maximum disconnection time. Say a circuit on a TN-C-S system would take 7 seconds to disconnect. That's because of a high resistance on the R1 + R2 side, or a high Ze. Either way, if Zs is too high, the fault current is low and disconnection is slow. An RCD for fault protection fixes this.

Watch out: disconnection times
A common mix-up is that maximum disconnection times range from about 0.1 to 2 seconds. For 230 V, Table 41.1 gives 0.4 s (TN) and 0.2 s (TT) for final circuits up to 63 A with socket-outlets or up to 32 A supplying fixed equipment. Distribution circuits and larger final circuits are allowed 5 s (TN) or 1 s (TT).

Any size will do, as long as it passes

For fault protection, the RCD can be any rating: 30, 100, 300 or 500 mA. Each has a maximum Zs:

Maximum Zs for each RCD rating
RCD rating IΔnIn amps (use this in the sum)Maximum Zs
30 mA0.03 A1667 Ω
100 mA0.1 A500 Ω
300 mA0.3 A167 Ω
500 mA0.5 A100 Ω

BS 7671 · Table 41.5 · maximum Zs for RCDs (1667 / 500 / 167 / 100 Ω)

BS 7671 lets you pick whichever one you like, as long as it passes this check:

RA × IΔn ≤ 50 V
RA can be swapped for your measured Zs. IΔn is the RCD's rating in amps: 0.03, 0.1, 0.3 or 0.5. Don't type in 30 or 500, or you'll get the wrong answer.

IΔn is written with a triangle (the Greek letter delta), not an "A" or an "E". It's said "I delta n". The maximum Zs values in the table are just 50 V ÷ IΔn. For example, 50 ÷ 0.03 = 1667 Ω.

BS 7671 · Reg 411.5.3 · RA × IΔn ≤ 50 V for TT systems

Example 1: commercial lighting circuit, Zs = 10 Ω

A lighting circuit in a commercial office on TN-C-S. Measured Zs = 10 Ω.
(10 Ω means something is seriously wrong, but go with it.)

Does it need additional protection?
  ✗ Not a socket-outlet
  ✗ Not a domestic lighting circuit
  ✗ Cables are on the surface in conduit and trunking (you can see them),
    so 522.6.202 and 522.6.203 don't apply. They're for hidden cables.
  → No 30 mA requirement. It needs FAULT protection only.

Check each size:  Zs × IΔn ≤ 50 V
  30 mA :  10 × 0.03 = 0.3 V  ✓
  100 mA:  10 × 0.1  = 1 V    ✓
  300 mA:  10 × 0.3  = 3 V    ✓
  500 mA:  10 × 0.5  = 5 V    ✓
→ Any of them is allowed.

Example 2: lighting in a barn on TT, Zs = 87 Ω

A lighting circuit in a barn in the middle of a field, on a TT system.
TT → it needs an RCD for fault protection. Measured Zs = 87 Ω (on a Monday).

  500 mA:  87 × 0.5  = 43.5 V  ✓ but sailing too close to the wind (max 100 Ω)
  300 mA:  87 × 0.3  = 26.1 V  ✓ still too close for comfort (max 167 Ω)
  100 mA:  87 × 0.1  = 8.7 V   ✓ our choice (max 500 Ω)
   30 mA:  87 × 0.03 = 2.61 V  ✓ but more sensitive than it needs to be

Why not the 500 or 300? Ground dries out:
  End of a hot week       Zs ≈ 107 Ω → 500 mA fails (107 × 0.5 = 53.5 V ✗)
  A month with no rain    Zs ≈ 207 Ω → 300 mA fails (207 × 0.3 = 62.1 V ✗)
                                      100 mA still fine (207 × 0.1 = 20.7 V ✓)
Zs 87 Ω (Monday) Zs 207 Ω (after a dry month) 0 V255075100 50 V limit 2.66.2 8.720.7 26.143.5 62.1 ✗ 103.5 ✗ 30 mA100 mA 300 mA500 mA ×0.03×0.1 · our pick ×0.3×0.5
Zs × IΔn in volts for the barn example. On Monday (87 Ω) every rating passes, but the 500 mA is already close to 50 V. After a dry month (207 Ω) the 300 mA and 500 mA fail. The 100 mA still has plenty of room.
Sparky's tip: TT fault protection
Don't pick a rating whose maximum Zs is close to your reading. Earth electrode resistance rises as the ground dries out. The 100 mA is a good usual choice: it's not too sensitive, and it leaves lots of headroom. Above about 200 Ω an electrode reading may not be stable, so look at improving the electrode too.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside