An RCBO looks almost identical to a circuit breaker. The difference is inside: it has an RCD built in, using a toroid coil rated in milliamps.

  • Ours is a B32, 30 mA: a Type B 32 A circuit breaker with a 30 mA RCD included, which makes it right for additional protection.
  • The RCD part is Type A: the symbol is a sine wave plus a pulsating-DC (half-wave) symbol. A plain sine wave on its own is the Type AC mark. Type A is now the most common type and is right for most circuits. Types B and F exist for more specific circuits.
  • You can still buy Type AC, but note that Chapter 53 of BS 7671 limits where AC can be used. Type A is the go-to.
Watch out: what Type A detects
A common mix-up is that a Type A detects "both AC and DC faults". Strictly, a Type A detects AC and pulsating DC residual currents. Only Type B detects smooth DC.

BS 7671 · Chapter 53 · Reg 531.3.3 · RCD types (Type AC only where the load has no DC components)

Wiring a CB versus an RCBO

Circuit breaker (CB) RCBO N bar E bar B32 busbar (line) from main switch to circuit N bar E bar flylead B3230 mA busbar (line) from main switch to circuit Only the LINE goes in the CB LINE and NEUTRAL go in the RCBO
With a CB, the circuit's neutral goes to the matching numbered terminal on the neutral bar (way 1 → neutral terminal 1) and the CPC to earth terminal 1. With an RCBO, the circuit's line and neutral go into the RCBO ("Load" and "N" terminals), and the RCBO's own fly lead goes to the neutral bar.
  • The RCBO clips on and is tightened exactly like a CB (with a torque screwdriver).
  • The blue fly lead connects to the neutral bar, in the terminal matching its way (ours is in way 2, so neutral terminal 2). It comes with slack. You can shorten it, but many people leave it so the RCBO can be moved around the board later. That's personal preference.
  • The CPC still goes to the earth bar, the same as every other circuit.

Why both line and neutral go through it

The toroid coil only works if both the line and the neutral pass through it. By Kirchhoff's current law, a healthy circuit has the same current in the neutral as in the line.

toroid coil (30 mA) load 10 A out → ← 9 A back 1 A 10 A ≠ 9 A → out of balance → TRIP earth fault: current has left a live conductor into an earthed part
Our numbers: a B32 RCBO with 10 A flowing. A healthy circuit has 10 A back in the neutral. If 1 A goes to earth, only 9 A returns and the RCBO trips very quickly. (A 30 mA device would trip long before a full 1 A leak.)

Our worked example: the out-of-balance coil

Healthy:      line 10 A → neutral 10 A   (Kirchhoff: in = out)
                difference = 10 − 10 = 0 A  → stays on
Earth fault:  1 A leaks into an earthed part
                neutral = 10 − 1 = 9 A
                difference = 10 − 9 = 1 A = 1000 mA
                1000 mA ≫ 30 mA  → trips very quickly
A CB has no toroid coil, so it can't see this imbalance.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside