R1 + R2 on a cooker circuit, tested from the frontDo you need to take the cooker switch off the wall?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

A cooker circuit is simpler: no lighting switches. Link line and CPC at the board as before, then prove the CPC at the cooker control unit and at the cooker outlet.

  • If the control unit has a socket-outlet, plug in the tester’s socket adapter and test line to CPC through the pins — with the socket’s own switch on. That proves the CPC is connected behind the plate without taking the plate off.
  • At the cooker outlet, probe the line and CPC terminals. Operate the cooker switch off and on: open circuit, then a reading.
Unscrew as little as you can. You opened the accessories once already, to inspect them. Every time you take a plate off and put it back you risk disturbing a conductor. Testing from the front proves the connection behind it.
✋And this is why you test. A CPC can be pulled off its terminal just by refitting an accessory — a cable catching as it’s pushed back in. The outlet reads open circuit, and nothing you looked at during inspection would have told you. A loose CPC on a cooker circuit is a metal appliance with no earth.

Easier still: if you can, ask the installer to leave the cooker unconnected until you’ve tested. Testing the cooker itself is in-service inspection and testing, a different job.

While you’re there: the socket on the control unit. It puts a socket-outlet on the cooker circuit, so the circuit needs 30 mA RCD protection under Reg 411.3.3. And a cable buried in a wall at less than 50 mm needs it too, under Reg 522.6.202 — or 522.6.203 in a metal-stud partition. That’s inspection, not this test, but it’s the kind of thing you notice here.

BS 7671 · Reg 411.3.3 · 30 mA RCD for socket-outlets BS 7671 · Regs 522.6.202, 522.6.203 · buried cables

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside