R1 + R2 on a cooker circuit, tested from the frontDo you need to take the cooker switch off the wall?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
A cooker circuit is simpler: no lighting switches. Link line and CPC at the board as before, then prove the CPC at the cooker control unit and at the cooker outlet.
- If the control unit has a socket-outlet, plug in the tester’s socket adapter and test line to CPC through the pins — with the socket’s own switch on. That proves the CPC is connected behind the plate without taking the plate off.
- At the cooker outlet, probe the line and CPC terminals. Operate the cooker switch off and on: open circuit, then a reading.
Easier still: if you can, ask the installer to leave the cooker unconnected until you’ve tested. Testing the cooker itself is in-service inspection and testing, a different job.
BS 7671 · Reg 411.3.3 · 30 mA RCD for socket-outlets BS 7671 · Regs 522.6.202, 522.6.203 · buried cables
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing