R1 + R2 at every point, and the highest readingFifty downlights. How many readings?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: Fifty downlights. How many readings? The answer is in the notes below.
The notes
Exactly as they are on the site.
With the link in, go to every point on the circuit: every luminaire, every switch, every socket, every outlet. At each one, one probe on the line terminal, one on the CPC terminal, press test.
Keep the highest reading in your head, or jot each one down. That highest reading is what you record as the circuit’s R1 + R2 on the schedule of test results.
- Expect low numbers on short runs. A short demonstration circuit can read a few hundredths of an ohm.
- Don’t be alarmed by an ohm or more on a long lighting circuit in 1 mm². Length and a small conductor both push resistance up.
- At a switch you are proving the CPC is there. One reading on a line conductor at the switch does it; the switch itself doesn’t need operating.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing