R1 + R2 as an inspector: Table B2B2 or B3 in an inspection exam?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Same calculation, different multiplier. This is what you'll need for your inspection and testing exams.

Designer
R1 + R2 = B1 × B3 × L ÷ 1000
Table B3 corrects to the operating temperature, because an earth fault only happens while the circuit is running.
Inspector
R1 + R2 = B1 × B2 × L ÷ 1000
Table B2 corrects to the ambient temperature on the day of the test.
1 · Design (January) in the office, on paper B1 × B3 × L ÷ 1000 B3: as if the circuit is on 2 · Install (March) the installer follows the design 3 · Verify (July, 40 °C) dead test, measured value B1 × B2 × L ÷ 1000 B2: the ambient on the day the inspector checks their corrected reading against the designer's value
A typical story. The design is done in January. Installation starts in March, and the inspector inspects as it goes, before floors, plaster and ceilings go in. Final testing is in July, in a boiling hot greenhouse or warehouse at 40 °C. The test is dead, so operating temperature doesn't matter, but the room temperature has warmed the conductors and changes the reading. Table B2 corrects for that.
A common mistake in design projects
On Level 4 design projects (and other design qualification projects), people include Table B2 in their R1 + R2 and get it referred. Table B2 corrects a test reading from 20 °C to the ambient temperature on the day. It's a test correction, not a design one. The designer's figure uses Table B3, for operating temperature. Table B2 is for the inspector on site, correcting the value they measured.

Guidance Note 3 · Table B2 "Ambient temperature multipliers (α) to Table B1" · p.175

Exam tip for initial verification and periodic inspection
When you're asked to calculate R1 + R2 in these exams, don't use Table B3. If the question gives an ambient temperature, include Table B2. If it doesn't, leave B2 out and just do B1 × L ÷ 1000.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside