Proving volt drop without a volt drop testNo volt drop test. Can you still prove it?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

The best thing here. There is no test for volt drop — but as the inspector you can still prove it is adequate, because almost everything you need is already on the certificate.

The scenario

4.0/1.5 mm² twin and earth, 25 m
16 A Type B, immersion heater
Reference method C (clipped direct)
Ze provided = 0.56 Ω

Step 1 — expected R1 + R2, from Table B1

4/1.5 = 16.71 mΩ/m

(16.71 × 25) ÷ 1000 = 0.4178  →  0.42 Ω

Step 2 — the cable's figures, from On-Site Guide · Appendix F · Table F6 (p.193)

4 mm², reference method C:

  It (tabulated current-carrying capacity) = 37 A
  millivolt drop per amp per metre         = 11 mV/A/m

Both are on the same row — the mV figure is the column
right next to the current rating.

Step 3 — the volt drop

volt drop = (mV/A/m × IB × length) ÷ 1000
          = (11 × 16 × 25) ÷ 1000
          = 4.4 V

5% of 230 V = 11.5 V     →  4.4 V is comfortably inside
Why IN can stand in for IB. Because IB ≤ IN. If you are given the device rating but not the design current, the device rating is the safe figure to use.

Step 4 — and the Zs that follows

Zs = Ze + (R1 + R2) = 0.56 + 0.42 = 0.98 Ω

16 A Type B, 80% value from OSG Table B6 p.159 = 2.19 Ω
0.98 Ω is well inside. Pass.
The only thing not on the certificate is the length

And you can get that too: measure R1 + R2, look up the mΩ/m in Table B1, and run the formula backwards. Cable type, reference method, device rating, RCD protection — all of it is on the paperwork already.

So volt drop is verifiable during inspection and testing, even though no instrument measures it. That is a genuinely useful thing to be able to do.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside