Proving dead: the three tests, and the rhythmWhich conductor does the first probe go on?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Put the probe on the conductor that should be at zero volts first — the neutral or the earth — and bring the second probe onto what would be live if it had not been isolated. No regulation says so. The reason is in your hand: do it the other way round and the free end of your lead is sitting on a line conductor while you are still reaching with it. Work from the least dangerous conductor first. The CPC is the safest, so that is where you start, and you move one probe at a time.

#Single phase — three tests
1CPC — Neutral
2CPC — Line
3Line — Neutral
Move one hand at a time. Never cross your arms over. Start on the safest combination and work along. Get a rhythm going and it is quicker — and you are not reaching across live terminals to do it.

Three phase is the same idea, ten readings: four to earth, three to neutral, three between lines. Start on earth, the safest conductor, and the line-to-line tests come last, because they are the most dangerous. Work up the list, not down it.

GroupThree phase — ten tests
1–4Earth to Neutral · Earth to L1 · Earth to L2 · Earth to L3
5–7Neutral to L1 · Neutral to L2 · Neutral to L3
8–10L1 to L2 · L1 to L3 · L2 to L3 — last

Lead colour does not matter on safe isolation or on dead testing. On live testing you line your colours up with the conductors. On phase rotation the order genuinely matters.

1–4  Earth to everything EN EL1 EL2 EL3 5–7  Neutral to each line NL1 NL2 NL3 8–10  Line to line — LAST L1L2 L1L3 L2L3 4 + 3 + 3 = 10 readings
Ten is easy to lose count of, so count it in groups: four off the earth, three off the neutral, then three between lines. The order is not arbitrary — you work out from the safest conductor, which is why the line-to-line tests are last. One probe moves at a time, and your arms never cross.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside