Everything up to here is one step of the eight. The installation being dead is what lets you do the rest safely; it is not the end of the check.

#What you doWhat you expect
3Clamp the earthing conductor and main bonding again, now it is offCurrent dropped to zero, or to an extremely small level
4Volt stick at the MET, along the earthing conductor, along each main bonding conductor, and at the extraneous-conductive-partsNo voltage indicated
5Disconnect the main protective bonding conductorsNothing unusual
6Volt stick again, same placesNo voltage indicated
7Reconnect the main protective bonding conductorsNothing unusual
8On a TN system, check the external earth fault loop impedance during your inspection and testingA sensible Ze — see below
✋Why a volt stick and not your AVI. While diverted current still has somewhere else to go, a two-pole voltage indicator will not see it. That is not a criticism of your tester — it is the physics. The book is explicit that a volt stick should be used as well. Not instead: as well.
Step 7 has a reason, and it is examinable. You put the bonding back so that insulation resistance testing can be carried out — the installation has to be connected to earth for that test. It is not tidiness. It is the next test on the sequence needing it.

Step 8 — and a number you have already met

As a rule of thumb, Ze up to about 0.35 Ω on TN-C-S and 0.80 Ω on TN-S. A reading that is high is the signal.

✋Read that as a rule of thumb, not a pass mark. You will have met 0.35 and 0.80 elsewhere as expected maximum values. Here the book says plainly that slightly higher readings may occasionally be experienced, and that comparing against previous readings tells you more than either figure. A 0.38 Ω TN-C-S reading is a reason to look harder, not a verdict.
And the honest framing. The book says there is no simple test that shows diverted neutral current, and that these eight steps are an example of an approach for dwellings — not a universal procedure. Know them as the shape of the check, and know why each one is there.

Guidance Note 3 · Appendix D · the eight steps

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside