The notes
Exactly as they are on the site.
Guidance Note 3 · p.88 and p.89 · section 2.6.16. On single phase this is easy — you take the loop test and press the button. On three phase the worst case is a fault across all three lines (about twice the single-phase value) — and measuring between line conductors may not be possible, and may not be safe.
Worked example
Measured line-to-neutral, one conductor at a time: L1 – N = 400 A L2 – N = 406 A L3 – N = 415 A <- the highest Take the highest and double it: 415 × 2 = 830 A = 0.83 kA
The reason it works: line to neutral is 230 V even on a three-phase supply, so each of those readings is taken at the same voltage. Doubling the worst one is a rule of thumb that errs on the side of safety.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing