Prospective fault current, on the same visitIs 297 the right number to write in the kA box?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
While you’re at the origin, you get the prospective fault current. It’s two readings, and the meter does the arithmetic (Ohm’s law) for you.
- PEFC — prospective earth fault current — comes with the Ze reading: same leads, line to earth.
- PSCC — prospective short-circuit current — probes on line and neutral on the supply side of the main switch. Read the current; ignore the ohms figure.
- Record the higher of the two as Ipf, in kA, on EIC page 2, just above Ze.
Jot it down as you go. A little table on scrap paper — Ze, PEFC, PSCC, and the same three at each sub-board — saves you remembering numbers while you move leads.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing