Prospective fault current: the three abbreviations
Prospective fault current is the current that would flow in the event of a fault — and it matters because every protective device has a limit on what it can interrupt without being destroyed.
| Abbreviation | What it is | Fault between |
|---|---|---|
| PEFC | Prospective earth fault current | Line and earth |
| PSCC | Prospective short-circuit current | Line and neutral |
| Ipf | What the schedule calls it | The greater of the two |
Breaking capacity: ICN and ICS
Guidance Note 3 · 2.6.16 has a table of short-circuit capacities, and the same table appears in the On-Site Guide. This is the one everybody asks about and nobody reads the facing column of.
| Marking | What it means |
|---|---|
| Icn | The maximum fault current the device can interrupt safely — but it may be destroyed doing it |
| Ics | What it can interrupt and still be usable afterwards, without replacement |
How they relate
A device marked Icn = 10 kA Ics might be stated as 7.5 kA, or as a percentage — some devices state Ics at 50% of Icn. So it will interrupt 10 kA once. Below Ics it survives to work again.
Typical capacities, from the table:
| Device | Breaking capacity |
|---|---|
| Rewirable fuse | Up to 4 kA, depending on designation (an S1A only 1 kA) |
| BS 1361 Type 2 — the main cutout fuse | 33 kA |
| Circuit breakers and RCBOs | 6 kA, 10 kA, up to 25 kA |
Using it: a worked judgement
Ipf at that point = about 7.3 kA (the measured maximum) Device on the board = Type B 32 A RCBO, 6 kA 6 kA < 7.3 kA -> not suitable on its own. You need the next rating up, 10 kA, unless a device on the supply side gives back-up protection (Reg 434.5.1) — domestic consumer units carry a conditional rating with the cut-out fuse.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing